problem
A stand-alone thermal management system for high heat-flux electronic components and laser diodes for the National Science Foundation.
solution
ACT has developed a Pumped Two-Phase cooling system for high heat flux electronic components and laser diodes, packaged in a compact, user-friendly, stand-alone solution. The two-phase system efficiently handles fluxes on ~ 300-500W/cm2, requires little pumping power, maintains device temperatures below operating limits, and provides for a high degree of isothermality over the heated surface. Meeting these requirements is important in many applications including lasers whose emission wavelengths are temperature-dependent.
how does it work?
Unlike single-phase cooling, two-phase systems take advantage of the phase change (latent heat) of the coolant which enables it to handle higher heat fluxes for a given heat load. Two-phase cooling systems can however be more complex and prone to flow and thermal instabilities. As such, techniques to effectively manage instabilities have been developed and characterized. These include the application of engineered microporous coatings on the heated surface(s), which enhance boiling performance by increasing the number of nucleation sites together with a capillary-driven resupply of the coolant to the heated surface, which prevents or postpones dry-out (extends CHF).
A schematic of a Pumped Two-Phase cooling system is shown in Figure 1. Key components include a pump, preheater, surge tank, evaporator (the heat sink), condenser and accumulator. The surge tank and the preheater differentiate this system from a traditional liquid cooling loop. The surge tank consists of vapor and liquid at saturation; by controlling the pressure in the tank, the saturation (boiling) temperature of the working fluid can be controlled. The preheater heats the subcooled liquid exiting the condenser to a temperature close to the saturation temperature before it enters the evaporator. This is important as boiling heat transfer is most efficient at saturation (minimal subcooling).
Figure 1: Schematic of a pumped two-phase cooling system
Also shown in Figure 2 is a representative copper minichannel heat sink coated with a microporous coating.
Figure 2: Minichannel heat sink with porous sintered power coating
The pumped two-phase cooling system shown in Figure 1 was fabricated and evaluated. The heat transfer coefficient (HTC) [W/m2K] and the Incipient Wall Superheat [K] were determined as a function of the input heat flux and coolant mass flux [kg/m2s] using refrigerant R134a and others. Representative results for the HTC for coated and uncoated minichannel heat sinks are shown in Figure 3. Clearly, the HTC is higher for the coated heat sinks and the CHF is extended.
Figure 3: Heat Transfer Coefficient (HTC) associated with Minichannel Heat Sinks noting the increase in CHF for coated heat sinks.
The incipient wall superheat is also shown in Figure 4 as a function of input heat flux on coated and uncoated heat sinks. Again, the microporous coating enhances the thermal performance of the heat sinks as evident by lower values of incipient wall superheat; in other words, a heat-generating device mounted on a two phase heat sink with microporous coating will be maintained at a lower temperature compared to one that is mounted on an identical uncoated heat sink.
Figure 4: Incipient wall superheat decreases with the application of microporous coatings
In addition to improving the heat transfer, the thin copper coatings help suppress two-phase flow instabilities. Figure 5 shows flow instabilities with a bare copper cold plate, where the vapor flow occasionally reverses and enters the input plenum. In contrast, instabilities are suppressed in the cold plate with a thin porous coating, see Figure 6.
Figure 5. High heat fluxes with uncoated mini- and micro-channel systems can have unstable flow. Note the intermittent vapor flow back into the inlet plenum.
Figure 6. The maximum heat flux in two-phase systems can be increased by adding a thin porous layer. An additional benefit is that the flow becomes more stable.
summary
In short, custom Pumped Two-Phase cooling systems have been developed. Flow and thermal stability issues were well managed with the use of porous coatings, which increase the heat transfer coefficient and extend the CHF. The pumping power required is minimal and the application of the coating does not increase the pressure drop in a measurable way as the coating thickness is very small compared to the channel dimensions. Additional work on flow boiling heat transfer in mini channel heat sinks is ongoing with a focus on maximizing performance and understanding the parameters (i.e., the coating properties – thickness for a given particle size, etc.) that affect performance for specific applications.
For more information on Pumped Two-Phase Cooling, contact ACT.