Sealed Enclosure Cooling from 22 Watts/°C to 68 Watts/°C
This passively sealed enclosure cooling device consists of two high-performance aluminum finned heat sinks bonded to the opposite sides of a common mounting plate. The HSC line has a high performance/cost ratio, due to the innovative use of advanced heat transfer and manufacturing technologies. ACT’s HSC units are easy to order online and offer fast shipping and easy control cabinet install. Perfect for automation equipment across various industries, anyone with a control cabinet will find one of ACT’s units to solve their thermal issue.
- Thin profile, i.e., only 3.70″ intrusion into the enclosure
- High performance, corrosion-resistant nickel-plated fins
- Few penetrations by cover fasteners, mounting fasteners, and external fan wires create an optimal seal
- Dual axial ball bearing fans for years of maintenance-free operation
- Rugged high-quality construction
- Easy to install
- 1-Year Warranty (see ACT’s Terms and Conditions)
- Order through our experienced sales staff or buy online
ACT-HEAT SINK COOLER (HSC) PRODUCTS
Part Number | Thermal Conductance Watts/°C | Thermal Capacity Watts @ 20°C Delta T | Weight*** lbs. (kg) | Height | Width | Depth* |
ACT-HSC-22** | 22.0 | 440 | 18.0 (8.2) | 12.00″ 304.8mm | 12.00″ 304.8mm | 7.88″ 200.1mm |
ACT-HSC-45 | 45.0 | 900 | 36.0 (16.3) | 21.75″ 552.5mm | 12.00″ 304.8mm | 7.8″ 200.1mm |
ACT-HSC-68 | 68 .0 | 1,360 | 52.0 (23.6) | 31.38″ 796.9mm | 12.00″ 304.8mm | 7.88″ 200.1mm |
Note: * Depth is total depth; insertion depth= 3.70″ into the cabinet. See the solid model in linked resources to the right for full-dimension details
** Shows dimensions for DC model in NEMA 3R, 4, 4X versions; check the solid model for other variants
***Weight for 4X models will be slightly greater
ACT-HSC MAXIMUM CURRENT DRAW BY MODEL
Model | ACT-HSC-22 | ACT-HSC-45 | ACT-HSC-68 | |
NEMA Rating | Voltage | Maximum Operation Current in Amps | Maximum Operation Current in Amps | Maximum Operation Current in Amps |
4, 4X, 3R (12) | 12VDC | 3.60 (3.90) | 7.20 (7.80) | 10.80 (11.70) |
4, 4X, 3R (12) | 24VDC | 1.64 (1.66) | 3.28 (3.32) | 4.92 (4.98) |
4, 4X, 3R (12) | 48VDC | 0.88 (0.92) | 1.76 (1.84) | 2.64 (2.76) |
4, 4X, 3R, 12 | 115VAC | 0.72 | 1.44 | 2.16 |
4, 4X, 3R, 12 | 230VAC | 0.38 | 0.76 | 1.14 |
ACT-HSC SERIES FEATURES AND OPTIONS
Environment | Indoor or Outdoor Use |
Electrical Configuration | 115VAC units arrive with a 6ft. long 3-pronged plug 230VAC, 12VDC, 24VDC and 48VDC units arrive with bare lead wires |
UL Listing & UL Recognition | The 115VAC units received a UL listing mark. All other versions are UL Rated/UL Recognized. (230VAC, 12VDC, 24VDC, and 48VDC) |
NEMA Options | 12, 3R, 4 and 4X, UL50E Certified |
Fans | UL Listed 6.0” dual ball bearing type axial fans (dry & wet locations) |
Mounting Plate | Aircraft quality 6061 aluminum |
HSC Housing | Powder-coated aluminum, Optional: stainless steel |
Mounting Options | Top, side, front, or back |
Operating Temperature | Range: 14°F to 140°F (-10°C to +60°C) |
Expected Fan Life | >100,000 Hours at 77°F (+25°C) |
Optional Accessories | Rain guards; removable filters (only needed for excessively dirty environments, i.e. desert or mining applications) |